Welcome to Ingeniería Algencal S.L.
Contact us at
+34 955513390

VMS

VMS

VMS

  • Electronic composite, up to 5 channels
  • Mixed combustion with up to 2 of 3 fuels with in-flight changeover
  • Connects to the control system
  • Simple to program
  • 10-bit resolution
  • Can be operated from PC
  • Optional charge controller
  • Integrated O2 controller
  • Type tested
FeatureValue

Power supply:

230 VAC +10 % -15 % 50/60 Hz
115 VAC +10 % -15 % 50/60 Hz (optional)

Ambient temperature
Operation:

+0 °C ... +60 °C

Ambient temperature
Transportation and storage:

-25 °C ... +60 °C

Resolution by analog input:

 

999 digits, 10 bits

Three-point pitch Recommended servomotor operating time:

30 s ... 60 s

Continuous output: Apparent ohmic resistance:

0 ... 10 V > 5 kΩ
0/4 ... 20 mA < 600 Ω

Digital signal input:

16 via floating contact
24 VDC or optional via 230 V module type 660R0018

Curve set number:

2 per channel (e.g., for dual gas/oil burner) optional 4 or 8

BUS connection:

25-pole Sub-D socket track

BUS card for the following systems:

  • INTERBUS-S (Phoenix)
  • PROFIBUS
  • Modbus
  • Ethernet (Modbus TCP)

Approvals:

EC Type Examination Certificate (Module B), according to Directive 2014/68/EU.

  • DIN EN 298:2012
  • DIN EN 1643:2001
  • DIN EN 230:2005
  • DIN EN 60730-2-5:2011
  • DIN EN 12067-2:2004
  • DIN EN 50156-1:2005, point 10.5

Confirmation SIL 3

  • DIN EN 61508:2011, Parts 2+3

EC Declaration of Conformity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 Mod. B+D)
  • 2009/142/EC (Gas Appliances Directive)
Product approved by:
en_USEnglish