Power supply:
From 115 VAC -15%
Up to 230 VAC +10% 50/60 Hz
Ambient temperature:
Operation:
+0 °C ... +60 °C
Transportation and storage:
-25 °C ... +60 °C
Resolution by analog input:
999 digits, 10 bits
Recommended: operating time of the positioning unit:
30 s ... 60 s
Constant outputs:
0 ... 10 V >5 kΩ
Load:
0/4 ... 20 mA < 600 Ω
Digital signal input:
14 (The line must not be longer than 10 m)
Digital outputs:
Main gas 1, main gas 2, oil valves, ignition valves, ignition transformer, fan, oil pump, failure
Number of sets of curves:
2 per channel (e.g. for combined oil/gas burner)
BUS coupling:
Through external adapter connected to LSB for these protocols:
Approvals:
EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive).
EC Type Examination Certificate according to 2009/142/EG (Gas Appliance Directive)
Confirmation SIL 3
EC Declaration of Conformity
System Acceptance Test - EN 50156-1 (TÜV)
Marine Type Approval Certificates GL and LR
AGA Certified Product - EN298, AS4625, AS4630