Welcome to Ingeniería Algencal S.L.
Contact us at
+34 955513390

ETAMATIC/ETAMATIC S

ETAMATIC/ETAMATIC S

ETAMATIC/ETAMATIC S

FeatureValue

Power supply:

From 115 VAC -15%

Up to 230 VAC +10% 50/60 Hz

Ambient temperature:

Operation:

+0 °C ... +60 °C

Transportation and storage:

-25 °C ... +60 °C

Resolution by analog input:

999 digits, 10 bits

Recommended: operating time of the positioning unit:

30 s ... 60 s

Constant outputs:

0 ... 10 V >5 kΩ

Load:

0/4 ... 20 mA < 600 Ω

Digital signal input:

14 (The line must not be longer than 10 m)

Digital outputs:

Main gas 1, main gas 2, oil valves, ignition valves, ignition transformer, fan, oil pump, failure

Number of sets of curves:

2 per channel (e.g. for combined oil/gas burner)

BUS coupling:

Through external adapter connected to LSB for these protocols:

  • INTERBUS-S (Phoenix)
  • PROFIBUS DPModbusEthernet (Modbus TCP)

Approvals:

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive).

  • DIN EN 298
  • DIN EN 1643
  • DIN EN 230
  • DIN EN 60730-2-5
  • DIN EN 12067-2
  • DIN EN 50156-1

EC Type Examination Certificate according to 2009/142/EG (Gas Appliance Directive)

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 1643
  • DIN EN 12067-2

Confirmation SIL 3

  • DIN EN 61508 Part 2+3

EC Declaration of Conformity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 Mod. B+D)
  • 2009/142/EC (Gas Appliances Directive)

System Acceptance Test - EN 50156-1 (TÜV)

Marine Type Approval Certificates GL and LR

AGA Certified Product - EN298, AS4625, AS4630

Product approved by:
en_USEnglish