GFI ignition systems

Sistemas de encendido GFI

GFI ignition systems

  • Low pressure loss through optimization.
  • Immediate and repeatable ignition at each combustion rate.
  • Maximum flame stability.
  • Safe flame monitoring.
  • Modular design.
  • Available in SIL 2 or SIL 3.
  • Intermittent or continuous operation.
  • Marine weather resistant aluminum or stainless steel type housing.
  • Protection class up to IP 67.
  • Thermal power up to 3,000 kW.
  • Flame length up to 2,500 mm.
  • Pilot burner length up to 15,000 mm.
  • Fuel: natural gas, LPG (liquefied petroleum gas), coke gas, refinery gas.
  • Individually customized solutions.
FeatureValue

Supply voltage:

220 - 230 VAC (-15/+10 %). 50/60 Hz.
120 - 127 VAC (-15/+10 %). 50/60 Hz.

Ignition voltage:

5 kV/10 kV.

Power consumption:

100 VA ignition transformer.
≤5 KV flame scanner.

Electrical connection:

Cable, pre-wired (standard), plug connector and socket with pre-assembled cable.

Cable length:

2 m - 100 m, standard = 5 m.

IP protection:

IP 65/IP 67.

Housing:

Sea water resistant aluminum (standard) stainless steel (1.4301/1.4404).

Coating:

none (standard)
C2/C4 paint (option).

Tube length:

240 - 15,000 mm, standard = 1,200 mm.

Tube:

Stainless steel 1.4301, heat-resistant end tube 14.841 (standard) Stainless steel 1.4571 heat-resistant end tube 14.841 (option).

Combustible gas:

Natural gas, propane/butane (standard) coke oven gas, refinery gas (option).

Fuel gas supply pressure:

50 - 200 mbar above combustion pressure (standard) Orifice for higher pressure (option).

Air supply pressure:

Depending on size.

Cooling air flow:

Depending on size, at least 50 % of the combustion air flow.

Approvals:

For SIL 2 ionization flame monitoring device:

kiwa 2009/142/EG.

kiwa Sil 2.

CE0063CR1400.

UL

IEC/IECEx, ATEX.

For flame monitoring device SIL 3 F130I:

2009/142/EC

2014/68/EU

SIL 3

 

Product approved by:
en_USEnglish